Re-Creating the IO Table in CX-Progammer
Scenario
The PLC IO table may need to be re-created for CX-ONE PLC's to accommodate the following situations:
- Replacing / Adding new IO Cards on existing installations
- To confirm IO addressing, if unable to transfer from PLC or is not backed up in project.
- To clear a particular defined IO Table Error on the PLC / specific card on the rack.
Solution
- Make sure PLC is in Program Mode. Select 'IO Table and Unit Setup':
- Highlight Rack where you want to recreate IO table. In this case select 'Main Rack'. Then select 'Options'->'Create':
- Create the IO Table. Select YES:
-
Decision TreeWhen asked to 'Initialise CPU Bus Settings':
-
Yes
-
No
- Add Button
select Yes if you want to initialise and factory default the rack.This content will be shown (depending on) when button above is clickedSelect Yes if you want to initialise and factory default the rack.Select NO to retain Special IO Cards memory
- Select Transfer, which will transfer IO table and all special IO unit parameters:
- IO table will be created on CPU and transferred from the PLC into CX-Programmer project: