How to Factory Reset a MX2 Inverter
To factory reset a MX2 Inverter use the following procedure:
Step 1: Set b084 to a value between 1 - 4 according to the table below. For a complete reset use 4.
Parameter No |
Function |
Monitor or Data Range |
Default Data |
---|---|---|---|
b084 |
Initialization Selection |
00: Initialization Disabled | 00 |
01: Clear Fault Monitor | |||
02: Initialize Data | |||
03: Clear Fault Monitor + Initialize Data | |||
04: Clear Fault Monitor + Initialize Data + Clear DriveProgramming |
Step 2: Set b180 to 1
The Inverter will begin initializing when finished it will display d001 on screen.