3G3M1-EMP EtherNet/IP to NX Example

Written by Nicolas Donoso

Updated at March 28th, 2026

Contact Us

If you still have questions or prefer to get help directly from an agent, please submit a request.
We’ll get back to you as soon as possible.

Please fill out the contact form below and we will reply as soon as possible.

  • Products
    Automation Systems Control Components Motion & Drives Quality control & Inspection Robotics Safety Sensing Services Software Switching Components
  • Amplify e-Store
    e-Store public
  • Public CSC
+ More

In this example we go through an example setup of 3G3M1-EMP Inverter with NX1P2 PLC using EtherNet/IP communication protocol

 

IP Address Configuration

For this example the static IP Address setup was 192.168.0.10/255.255.255.0.

To assign the IP address in static mode, connect via USB using Sysmac Studio and enter the desired IP address in the parameters within the o2xx list when parameter o213=0.

You can also chose to set the IP Address by using the Rotary Dials instead, if so you need to set parameter o213 = 1.

Set parameter o214 = 2 to select the protocol to be EtherNet/IP and set o299 = 1 to apply the settings. After this power cycle the Inverter.

 
 

EtherNet/IP - Input-Output Communication Assemblies

This can be referenced from the manual “ Multiprotocol Ethernet® Communication Type 3G3M1-EMP Ethernet Functions.”

In this example, the 8 BYTE Assemblies, 117 Output (Writing from the PLC to the Drive), and 167 Input (Reading from the PLC to the Drive) will be used.

 
 

M1-EMP Parameter Configuration in Sysmac Studio

USB Connection to M1-EMP

USB port with a female MICRO USB connector, which allows connection to a PC USB port.

 
 

Open a project in Sysmac Studio

You must use either Sysmac Studio Drive Edition or Sysmac Studio Standard Version. Software version must be 1.64 or above.

Select device type: Drive and model 3G3M1.

 
 

Verify Serial Device (COM__)

Verify in Windows Device Manager on which USB Serial Device (COM__) port the cable connected to the M1-EMP is located.

 
 

Configure the device’s USB connection

Right-clicking the device and selecting Configuration Settings.

 
 

Set the COM port

 
 

Go online with Inverter

 
 

Setup and tuning

Section where essential parameterization for the application type can be performed easily, to do this, right-click on the device and select Setup and Tuning.

 
 

Ethernet Reference

Configure the drive to receive frequency setpoints and the Run command via Ethernet communication.

 
 

Transfer parameters to Inverter

Configure the remaining parameters required for the application and transfer the changes to the device. 

Perform a power ON/OFF cycle of the device to apply all changes.

 
 
 
 

NX1P2 Configuration

Create Structure DataType - Output Data

 
 

Create Structure DataType - Input Data

 
 

Create published variables

 
 

Synchronize with NX1P2

Before setting up the EtherNet/IP Data Tag Link setting, transfer the program to the PLC first.

 
 

EtherNet/IP Connection Settings

Right-click on the port and select “Edit”

 
 

Add EDS Files

Right-click in the Target Device area of the workspace and select “Display EDS Library”

Install the EDS files for the 3G3M1-EMP Inverters

 
 

Add Target Device

 
 

Register Publish Variables

Select “Register All” to register the variables created in previous step.

 
 

Link variables with Target Device

In the central window under the Connection menu, add the target device or drag the one displayed in the tool window.

 
 

Transfer EtherNet/IP setting to PLC

 
 
 
 

Test communications

Once transferred and with the CPU in RUN, open a watch window to write and monitor the program variables.

 
 

 

ethernet/ip nx example 3g3m1 m1 3g3m1-emp