How to determine the route path for NX/NJ PLCs

Written by Arlo D'Cruz

Updated at April 18th, 2023

Contact Us

If you still have questions or prefer to get help directly from an agent, please submit a request.
We’ll get back to you as soon as possible.

Please fill out the contact form below and we will reply as soon as possible.

  • Products
    Automation Systems Control Components Motion & Drives Quality control & Inspection Robotics Safety Sensing Services Software Switching Components
  • Amplify e-Store
    e-Store public
  • Public CSC
+ More

What is a Route Path?

In CIP communication, the PLC is instructed on how to transmit the message from its CPU through the network and to the destination device's CPU using a route path. The route path consists of three primary components: the path for leaving the client PLC, the IP address of the target PLC, and the path for reaching the target PLC's CPU. 


Determining the route path for a simple system

In a straightforward setup, such as when a NX102 client communicates with a NX102 server, the route path can be quite simple. To ensure that the message is transmitted via the Ethernet port, the first component of the route path should be set to 02. The second component is the IP address of the server, let's say it is 192.168.250.2. Therefore, the complete route path becomes 02\192.168.250.2. On Omron PLCs, when communicating with the primary network port of the server PLC, the third component of the route path is not necessary. Hence, the final path would be 02\192.168.250.2. 

Network type number: "02" (Output the command via the built-in EtherNet/IP port)
• Destination address: Specify the destination IP address
• Route path: 02\192.168.250.2

Delete

Determining the route path for a complex system

In more intricate systems, EtherNet/IP adapters such as the CJ1W-EIP21 may be incorporated alongside an NJ CPU. In such cases, it becomes necessary to update the path to guide the client on how to route the data to the server CPU. The message must traverse through the backplane, the appropriate EtherNet/IP card, and the right device on the network before proceeding to the backplane and eventually to the server CPU.

When selecting the appropriate EtherNet/IP card, it's essential to note that the route path entry will use the Unit number + 10hex to identify the correct device. For instance, in the example provided earlier, the route path entry for EtherNet/IP Unit 1 was "#11" (Unit number: 1+10 hex). 

Here's an example of how it would appear:
 

CPU Unit 1 to EtherNet/IP Unit 1:

  • Network type number: "01" (Output the command via the internal backplane port)
  • Destination address: "#11" (Unit address of EtherNet/IP Unit (Unit number: 1+10 hex))

From EtherNet/IP Unit 1 to EtherNet/IP Unit 2:

  • Network type number: "02" (Output the command via the EtherNet/IP port)
  • Destination address: Specify the destination IP address

From EtherNet/IP Unit 2 to CPU Unit 2:

  • Network type number: "01" (Output the command via the internal backplane port)
  • Destination address: "#00" (Unit address of the CPU Unit)
Route path: 01\#11\02\192.168.250.2\01\#00
Delete



cip route path

Was this article helpful?

Yes
No
Give feedback about this article

Related Articles

  • Do I need Power Supply units for my NX CPU?
  • Error codes in Sysmac Studio
  • Major or Minor Revision mismatch for EtherNet/IP Error 0116
  • Ethernet/IP Setup Guide Using Network Configurator
  • EtherCAT Ring Topology FAQ

Definition by Author

0
0
Expand